[艾尔电气 介损测试仪 执行标准]
|
DL/T962-2005
|
|
[艾尔电气 介损测试仪 产品简介]
|
全自动抗干扰异频介损测试仪,是一种测量介质损耗角正切和电容值的自动化仪器。可以在工频高电压下, 现场测量各种绝缘材料、绝缘套管、电力电缆、电容器、互感器、变压器等高压设备的介质损耗角正切和电容值。与西林电容电桥相比,具有操作简单、自动测量、读数直观、无需换算、精度高、抗干扰能力强等优点。仪器内部有标准电容器和升电压装置,在“内接”方式下使用,无需其它外接设备,便于携带。
|
|
|
[艾尔电气 介损测试仪 产品特征]
|
1、具有多种测量方式,可选择正/反接线、内/外标准电容器、CVT测量和内/外试验电压测量。
2、抗干扰效果好:能有效地消除强电场干扰,适用于500KV及以下电站干扰现场的试验。
3、高压短路和突然断电时,仪器能迅速切断高压,并发出警告信息。
4、测量重复性好,电压线性好(测量准确度不受电压影响)。
5、一体化结构,重量适中,便于携带。
5、大屏幕中文提示操作,使用方便。
6、自带打印机,及时打印测试数据。
|
|
[艾尔电气 介损测试仪 产品参数]
|
1.
|
使用条件
|
-5℃∽40℃
|
RH<80%
|
2.
|
电 源
|
AC 220V±10%
|
频率无限制
|
3.
|
高压输出
|
1KV∽10KV
|
每隔1kV
|
|
|
精 度
|
5%
|
|
|
****电流
|
140mA
|
|
|
容 量
|
1000VA
|
5.
|
自激电源
|
AC 0V∽30V
|
45HZ/55HZ
|
|
|
****电流
|
15A
|
6.
|
分 辨 率
|
tgδ: 0.001%
|
Cx: 0.1pF
|
7.
|
精 度
|
△tgδ:±(读数*1.0%+0.040%)
|
|
|
△C x :±(读数*1.0%+1.0PF)
|
8.
|
测量范围
|
tgδ
|
无限制
|
|
|
C x
|
15pF<Cx<100000 pF
|
|
|
|
10KV
|
Cx<30000 pF
|
|
|
|
5KV
|
Cx<60000 pF
|
|
|
|
1KV
|
Cx<100000 pF
|
|
|
CVT测试
|
Cx<100000 pF
|
9.
|
外型尺寸
|
470(L)×320(W)×390(H)
|
10.
|
重 量
|
30 Kg
|
|
|
|
根据用户具体要求,设计相应的产品配置方案。
|
|
AL112 Dielectric loss tester
Implementation of standards.
DL/T962-2005
The series of equipment, which is mainly used in HV substation engineering project or in test room, gives a precision test on capacity, inductance and dielectric loss of HV capacitive and inductive test object.
1. Main components of the equipment:
HV variable frequency power supply to provide test signal for internal HV test mode
Built-in standard capacitor served as test reference in the mode of inner standard
Digital HV capacitive bridge served as main circuit of sample and measurement
High speed processing unit of digital signal high speed FFT transformation and digital filtering of the sampled signal
Controlling system realizing full-auto intelligent test
Key technology :
Adopt digital frequency technology; application of double frequency 45Hz/55Hz test avoids interference from 50Hz power network, thus making test results of high accuracy possible under interference of 50Hz high electric field in test site.
When in internal HV test mode, keep a track of frequency of power network, in accordance of which frequency of test signal is determined, and at the same time FFT frequency keeps a strict pace with test signal frequency, thus guaranteeing a perfect result in suppression of 50Hz/60Hz power network interference. For the algorithm, it will ensure a throughout elimination of interference from power network, with theoretical residue being 0.
The adoption of synchronous sampling technology presents a simultaneous sampling on two-way of test signals of standard circuit and measuring circuit, greatly improving measuring accuracy of dielectric loss.
Function and index
1. Basic function
Test of dielectric loss of CVT equipment through self-excitation;
Built-in standard capacitor
Grounded connection and ungrounded connection for selection
Three modes of tests for selection, internal HV single-frequency test, internal HV variable frequency test and external HV test;
In an external HV test, keeping track of its frequency which is strictly equal with external HV frequency;
Test procedure: retarded voltage step-up─>measurement─>voltage step- down─>display test result;
Built-in microprinter synchronizes printing of test result and follow-up test;
Through man-machine interface, data of current ambient temperature and humidity are input, which can be saved and printed together with test result;
Grounded protective detection: start ground protection when enclosure charges dangerous voltage due to poor grounding of equipment;
Over current protection: capable of effective quick protection and not causing human danger and equipment damage, when over current emerges from short circuit of test object and test wire touching ground.
2. Main technical index
Capacitive test
Test range: 10pF-63000pF varying from model to model
Test accuracy: ±(reading ×1%+1pF)
s resolution: 0.01pF
Dielectric loss test
Test range: 0-50%
Test accuracy: ±(reading×1%±0.0004)
resolution: 0.001%
Detecting range of current of test object: 31uA-1A
Frequency tracking: range 45Hz-65Hz
Power source of internal HV test: nominal frequency 50Hz, 60Hz
Internal HV output frequency is related to power network owing to application of power network tracking technology.
When setting the test frequency, actual output frequency of internal HV and frequency of power network conform to the following ratio: 90%、100%、110%、120%
For example, when frequency of power network is at 60Hz:
When set at 60 single frequency, actual output frequency is 60×100%=60Hz
When set at 54Hz\66Hz double frequency, actual output frequency is 60×90%=54Hz and 60×110%=66Hz
Voltage range: 0.5-10kV
Voltage setup: 0.5kV stepping
Voltage displaying range: 0.1-9.99kV
Voltage displaying accuracy: ≤±(1.5%×reading+5V)
Max output current: 200mA
Rated output power: 500W-2000W varying from model to model
Running method: continuous running for ≤15min
Power source of CVT test: auxiliary winding output of power source of internal HV test is used as the power source of CVT test.
Output voltage: ≤50V
Output current: ≤15A
Test voltage: ≤3000V
Power supply:
Voltage: 220V±10%
Frequency: 50Hz±0.5Hz/60Hz±0.6Hz
Ambient condition:
Temperature range: -10℃~55℃
Relative humidity:<90%